Cooling Tower Design and Selection: Open Towers, Closed Circuit Coolers and CTI Compliance

Heat Rejection

Cooling Tower Design and Selection: Open Towers, Closed Circuit Coolers and CTI Compliance

How cooling towers reject heat, the terms every selection depends on, and how CTI certification works, plus what's new in our Cooling Tower Selection and Cooling Tower Design software.

Applied Engineering Team
Oct 17, 2026
13 min read

Introduction to Cooling Towers

Cooling towers reject heat from chillers, industrial processes and power plants more efficiently than almost any?other method, because they use evaporation. That same principle makes their selection less intuitive than a dry?heat exchanger: performance depends on the wet-bulb temperature of the air, not only on its dry-bulb?temperature.

How a cooling tower works

Warm water is distributed over a heat transfer surface while air is drawn through the tower. A small part of the?water evaporates, and the heat needed for that evaporation is taken from the remaining water, which leaves the
tower cooler.
Because the process is evaporative, a cooling tower can cool water below the ambient dry-bulb temperature. Its?theoretical limit is the wet-bulb temperature of the entering air.


Three types of equipment
  • Open cooling tower: The process water is in direct contact with the air as it flows over the fill. The most?compact and lowest-cost way to reject heat.
  • Closed-circuit fluid cooler: The process fluid stays inside a coil. A separate spray water circuit wets the?outside of the coil, so the process loop stays clean.
  • Evaporative condenser: Refrigerant condenses inside the coil, combining the condenser and the cooling tower in one unit.

Flow arrangements
  • Counter-flow: air moves upward against the falling water. Compact, with good thermal performance for its?footprint.
  • Cross-flow: air moves horizontally across the falling water. Gravity water distribution, low pump head and?easy access for maintenance.
  • Mixed-flow: combines both paths to balance performance, footprint and pumping.
Closed-circuit units can be built with or without fill. Adding fill alongside the coil increases the wetted surface?and the heat transfer per unit of footprint.


The terms every selection uses
  • Range: Hot water temperature minus cold water temperature.
  • Approach: Cold water temperature minus the entering air wet-bulb temperature.
  • Design wet bulb: The entering air wet-bulb temperature the tower is sized for.
  • L/G ratio: Water mass flow divided by air mass flow.
  • Drift: Water droplets carried out with the air, limited by drift eliminators.
  • Make-up water: Water added to replace evaporation, drift and blowdown.
Tower size rises steeply as the approach gets smaller, so the approach is the single most important selection?decision.


CTI testing and certification
The Cooling Technology Institute ?CTI? publishes the codes and certification programmes the industry uses to?prove thermal performance:
  • CTI ATC-105: the acceptance test code for measuring the thermal performance of a cooling tower in the?field.
  • CTI STD-201: the standard for the thermal performance certification of evaporative heat rejection equipment,based on independent testing of a manufacturer's product line.
For a manufacturer, certification means every published rating must be reproducible by test. That only works?when the selection method behind the catalogue is consistent and validated.


Beyond the thermal design
A tower that meets its thermal duty can still fail in operation if its components aren't selected together:
  • Fan: selected at the real air flow and static pressure of the tower.
  • Spray system and nozzles: sized for even wetting of the fill or coil at the design water flow.
  • Pump: selected for the spray water flow and the head of the distribution system.
  • Drift eliminator: limits water loss and keeps droplets out of the surroundings.

Our cooling tower software
We offer two tools for cooling towers, and both have just been updated.

Cooling Tower Selection
Open and closed-circuit cooling towers, selected to CTI.
  • Open towers, closed-circuit fluid coolers and evaporative condensers
  • Counter-flow, cross-flow and mixed-flow designs, with or without fill
  • Evaporative condenser mode with 210? refrigerants
  • Fan, pump and drift eliminator selection
  • Built-in CTI 105 / CTI 201 compliance check, supporting CTI certification
  • Performance validated against lab tests by many manufacturers
  • Optional performance tables and charts across approach and range
Cooling Tower Design
  • Open and closed-circuit cooling towers, from thermal design to CTI compliance.
  • Open towers, closed-circuit fluid coolers and evaporative condensers
  • Counter-flow, cross-flow and mixed-flow designs, with or without fill
  • Complete tower sizing: dimensions, fill, spray system, fan, pump and drift eliminator
  • Flexible rating and sizing modes to match any project brief
  • Built-in CTI compliance check, supporting CTI 105 / CTI 201 certification
  • Optional 3D tower and coil manufacturing drawings with bill of materials

What's new in this update
  • Face velocity: a new face velocity input for more accurate and flexible design.
  • Cooling pad selection in three modes: known cooling water in; unknown water in with known water out; or?unknown water in and out.
  • Fan selection from Ziehl-Abegg, ebm-papst and Weiguang.
  • Nozzle, pump and dimension calculation, with a technical report and CAD drawing for every design.

Key takeaways
  • Cooling towers use evaporation, so their limit is the entering wet-bulb temperature.
  • Open towers, closed-circuit fluid coolers and evaporative condensers suit different processes.
  • The approach drives tower size more than any other parameter.
  • CTI ATC?105 and STD?201 are how thermal performance is proven and certified.