CRAC vs CRAH: Computer Room Condensing Units and Air Handlers Explained

Data Center Cooling

CRAC vs CRAH: Computer Room Condensing Units and Air Handlers Explained

Computer rooms need cooling that runs every hour of the year with tight control. Here is how CRAC units with condensing units and chilled-water CRAH units work, how they compare, and what to check when you design or select one.

Applied Engineering Team
Oct 18, 2026
12 min read

Introduction to Computer Room Cooling

Almost all of the electrical power drawn by IT equipment ends up as heat in the room. That heat has to be removed continuously, 24 hours a day, 365 days a year, with enough redundancy that a single failure never shuts the room down.

Two families of precision cooling units do most of this work: CRAC units (computer room air conditioners), which have their own refrigeration cycle and reject heat through a condensing unit, and CRAH units (computer room air handlers), which use chilled water from a central plant.


Why computer rooms need dedicated units

Comfort air conditioners are designed for spaces with people, where a large part of the load is latent (moisture).A typical comfort unit has a sensible heat ratio SHR of around 0.7 to 0.8, so a fifth or more of its capacity goes into removing moisture.

A computer room load is almost entirely sensible. Precision units are designed for:

  • A high sensible heat ratio, typically 0.9 or higher
  • High airflow per kW of cooling, to carry heat away from dense equipment
  • Continuous operation and a long service life
  • Tight temperature and humidity control
  • Redundant configurations such as N+1


CRAC units and condensing units

A CRAC unit is a direct-expansion DX air conditioner. The compressor, evaporator coil, expansion device and fans are typically housed in the indoor unit, which sits in or next to the computer room.

The heat collected in the room is rejected outdoors in one of two ways:

  • Air-cooled: refrigerant is piped to a remote air-cooled condenser or condensing unit outdoors.
  • Water- or glycol-cooled: a condenser inside the unit rejects heat to a water or glycol loop, which is cooled by a dry cooler or cooling tower.


CRAC units suit small and medium rooms, edge sites and buildings without a chilled water plant. Each unit is self-contained, which simplifies phasing and redundancy. Their limits are the efficiency of many small compressors at large scale, and the maximum refrigerant pipe length and height difference between the indoor unit and the condenser. Some DX units add a pumped-refrigerant or glycol free-cooling stage to reduce compressor running hours in cool weather.


CRAH units

A CRAH unit has no compressor. It moves room air across a chilled water coil, and a modulating valve controls how much chilled water flows through the coil. The cooling itself is produced by central chillers.

CRAH units are usually the more efficient choice at large scale, especially when the chilled water temperature is raised. Warmer chilled water improves chiller efficiency and increases the number of hours that free cooling can cover. Their limits are the need for a chilled water plant, and water piping in or near the IT space, which must be designed with leak detection and isolation.


CRAC vs CRAH at a glance

  • Cooling source:

  1. CRAC: Its own DX refrigeration cycle
  2. CRAH: Chilled water from a central plant

  • Compressor in the unit:

  1. CRAC: Yes
  2. CRAH: No

  • Heat rejection:

  1. CRAC: Remote condenser or condensing unit, or a water/glycol loop
  2. CRAH: Through the chiller plant

  • Typical application:

  1. CRAC: Small and medium rooms, edge sites, no chilled water
  2. CRAH: Medium and large data centers with a chiller plant

  • Capacity control:
  1. CRAC: Variable-speed or staged compressors, and fan speed
  2. CRAH: Chilled water valve and fan speed

  • Free cooling:

  1. CRAC Optional pumped-refrigerant or glycol economizer
  2. CRAH Water-side economizer, more hours with warmer chilled water

  • Main design limits:

  1. CRAC Refrigerant pipe length, efficiency at scale
  2. CRAH Dependence on the plant, water near the IT space


Design conditions

The ASHRAE TC 9.9 thermal guidelines define a recommended envelope for the air entering IT equipment of 18-27C dry bulb. The recommended humidity range is defined by dew point, from -9C to 15C, with an upper limit of 60% relative humidity.

Two practical consequences:

  • Control the unit on supply or rack inlet temperature, not on return temperature. IT equipment only cares about the air it takes in.
  • Avoid over-cooling and unnecessary dehumidification. Both waste energy without improving reliability.

Always confirm design values against the current edition of the ASHRAE guidelines and the IT equipment manufacturer's requirements.


Air distribution and containment

How the air reaches the racks matters as much as the unit's capacity.

  • Raised floor (downflow): units supply air under the floor, and perforated tiles deliver it to the cold aisles.
  • Upflow or ducted: units supply air through overhead ducts or directly into the room.
  • In-row: smaller units sit between the racks, close to the heat source.
  • Containment: physically separating hot and cold aisles stops the air from mixing. Higher, more stable return temperatures increase the sensible capacity and efficiency of both CRAC and CRAH units.


Selection checklist

  1. Sensible capacity at the actual return air conditions, not nominal total capacity.
  2. Airflow at the real external static pressure of the floor plenum, ducts and filters.
  3. Condensing unit performance at the design outdoor temperature, including high-ambient sites such as the Gulf, where summer design temperatures can exceed 46C.
  4. Redundancy (N+1 or higher) and how the room behaves when one unit fails.
  5. Fans: EC fans with speed control for part-load efficiency.
  6. Refrigerant: the move from R410A to lower-GWP options such as R32 or R454B (A2L, mildly flammable) brings new safety requirements to check.
  7. Rated performance: AHRI Standard 1360 and ASHRAE Standard 127 for computer room units in North America, EN 14511 in Europe, and ASHRAE 90.4 for data center energy requirements.


Common mistakes

  • Selecting on total capacity when the load is almost all sensible.
  • Sizing condensers at a mild ambient temperature and losing capacity on the hottest days.
  • Placing condensers where they recirculate their own hot discharge air.
  • Leaving gaps that let cold air bypass the racks or hot air return to the inlets.
  • Units fighting each other, with one humidifying while another dehumidifies.


CRAC Selection

Computer-room units selected for reliable, around-the-clock cooling.

  • Air-cooled and water-cooled computer-room units, including heat-pump versions
  • Wide range of refrigerants
  • Hot-climate ready: ambient up to 55 °C. Low-temperature applications down to −80 °C are also supported
  • Automatic check that every component runs within its limits
  • Seasonal efficiency: ISEER, IPLV, NPLV and Ecodesign
  • Wide range of power supplies


Key takeaways

  • Computer room loads are almost entirely sensible, so precision units are built for a high SHR and continuous duty.
  • CRAC units carry their own refrigeration cycle and reject heat through a condensing unit; CRAH units use chilled water.
  • CRAC suits smaller, independent sites; CRAH is usually more efficient at scale.
  • Containment and inlet-temperature control matter as much as unit capacity.